VI FCP-L2/8 ADDRESSABLE FIRE ALARM CONTROL PANEL
FEATURES
- EN54-2 & EN54-4 certified by LPCB and Applus.
- 7.0 inch color touch-sensitive screen LCD,resolution of 800×480.
- 324 addresses for 1 loop, max 8 loops.
- A maximum of 5000 fire protection zones are supported. More user-friendly. Night Mode Time Range Settings.
- Networkable: CAN bus for interconnection of up to 60 FACPs and Ethernet for up to 254 FACPs.
- Fire alarm, fault, C&E and operation,each category can store up to 10,000 records.
TECHNICAL SPECIFICATIONS
| Mains supply | 110/230V AC (-15%,+10%), 50Hz/60Hz |
| Fuse rating | T4A250V |
| Max. battery capacity | 24AH - 38AH |
| Max. charging current/voltage | 1A / 28V ± 0.5VDC |
| Max. integrated resistance | 1Ω |
| Fire alarm output | 20 ~ 28 V DC |
| F.P.E. output | 20 ~ 28 V DC |
| Probe Output Circuit Output | 20 ~ 28 V DC |
| Fire alarm output | 18 ~ 28V DC, 50mA, 10KΩ |
| Fault output | 2A @ 24VDC (NC, COM, NO) |
| 24V (+, -) | 20 ~ 28VDC |
| Output current/voltage | Max. 2A (AUX 24V) 1A (S.C. Out) |
| Dimensions (WxHxD) | 440×400×180mm |