VI FCP-L2/4 ADDRESSABLE FIRE ALARM CONTROL PANEL

VI FCP-L2/4 ADDRESSABLE FIRE ALARM CONTROL PANEL

FEATURES

  • EN54-2&EN54-4 certified by LPCB and Applus.
  • 7.0 inch color touch-sensitive screen LCD, resolution of 800×480.
  • 324 addresses for 1 loop, max 4 loops.
  • A maximum of 5000 fire protection zones are supported. More user-friendly Night Mode Time Range Settings.
  • Networkable: CAN bus for interconnection of up to 60 FACPs and Ethernet for up to 254 FACPs.
  • Fire alarm, fault, C&E and operation, each category can store up to 10,000 records.

TECHNICAL SPECIFICATIONS

Mains supply 110/230V AC (-15%,+10%), 50Hz/60Hz
Fuse rating T4A250V
Max. battery capacity 2×12V/12Ah Battery 1A
Max. charging current/voltage 1A / 28V ± 0.5VDC
Max. integrated resistance
Fire alarm output 20 ~ 28 V DC
F.P.E. output 20 ~ 28 V DC
Probe Output Circuit Output 20 ~ 28 V DC
Fire alarm output 18 ~ 28V DC, 50mA, 10KΩ
Fault output 2A @ 24VDC (NC, COM, NO)
24V (+, -) 20 ~ 28VDC
Output current/voltage Max. 2A (AUX 24V) 1A (S.C. Out)
Dimensions (WxHxD) 440×400×180mm